DIY residential off-grid setup · 48 V with grid backup
Project Anor
Two Victron inverters on one shared battery. A Multi RS Solar runs the light loads from its own panels. A MultiPlus-II runs the heavy loads, fed by two separate solar charge controllers. Grid is the backup for both.
Wiring schematic
The install
A DIY install, planned, built and wired by bigbrovar. The Multi RS Solar and MultiPlus-II share a steel rack with the two SmartSolar chargers above them and the breaker and distribution boxes below. The four battery packs stand stacked on the floor beside the rack.
The layout at a glance
Two AC islands
Light loads sit on the Multi RS. Air conditioners, the borehole pump, cooking and water heating sit on the MultiPlus-II. Each side has its own breaker, surge protector and RCBO board.
Two ways in for solar
13 panels go straight into the Multi RS’s two built-in trackers at high voltage. The other 18 go through two SmartSolar chargers, one 250 V and one 150 V, straight into the batteries.
One shared battery bank
Four 14.7 kWh packs are joined on one set of copper bars, called a busbar. Every charger and inverter connects to those bars through its own DC breaker. A SmartShunt and a small home-built monitoring computer (the GX) keep track of the whole bank.
Sizing checks
Do the strings and breakers suit the equipment they feed? Each check is worked out live from the datasheet numbers in the parts list, so it updates whenever the data does.
Panels make more voltage in the cold, so voltage limits are checked at the coldest cell temperature you expect.
Battery side
How these are worked out
- Cold voltage:
Voc × panels in series × (1 + |temp. coeff.| × (25 °C − coldest °C)), compared with the charger’s absolute maximum PV voltage. The temperature coefficient comes from each panel’s datasheet. - Short-circuit current:
Isc × strings in parallel, compared with the charger’s maximum PV short-circuit current. - Working current and panel power: compared with what the charger or tracker accepts. Going over isn’t unsafe; the charger trims the excess, which is called clipping.
- String fuses and breakers: IEC 62548 puts their rating between
1.5 × Iscand2.4 × Iscof one panel, and no higher than the panel’s maximum series fuse rating. - Surge protectors: their rated DC voltage should stay above the string’s cold open-circuit voltage.
- Battery side: charger breakers at 1.25 × the charge current; inverter draw at a near-empty 48 V and about 94% efficiency; current shared evenly across the packs.
A sanity check for readers, not a substitute for a qualified installer or Victron’s own sizing tools.